PP-R vs PEX for water supply in hot climates

Published: · BR BORLINE

Both PP-R and PEX are proven plastics for hot and cold water inside buildings. In the Gulf and Iraq the decision usually comes down to jointing, heat and how the pipe is installed.

Standards

PP-R systems are covered by ISO 15874 and PEX (PE-X) systems by ISO 15875. Both standards define application classes for hot and cold water and heating; neither material is “unstandardised”.

Jointing

PP-R pipes and fittings are joined by socket fusion: the parts are heated (our catalogue specifies 260 °C) and pushed together, becoming one piece of plastic. PEX cannot be joined by solvent cement or typical heat fusion; it uses mechanical fittings — crimp, clamp, press or expansion rings. Fusion joints have no O-ring or metal ring to fail behind a wall; mechanical PEX joints need no welding tool and are fast to make. The right choice depends on your installers’ tools and training.

Heat and pressure

For PP-R, allowable pressure falls with temperature: per DIN 8077 (safety factor 1.5) a PN20 pipe is rated 12.9 bar at 60 °C and 8.5 bar at 70 °C for 50 years. In hot climates, water in rooftop tanks and exposed lines can become hot even in the “cold” network, so specifying PN20 or composite pipe for any line that may run hot is a sensible margin. See our PN rating guide.

Sunlight

Neither material should be left exposed to direct sunlight. The Plastics Pipe Institute advises that PEX should not be installed outdoors unless buried or protected from UV, and its PP model specification calls for UV protection where PP pipe will be exposed to direct sunlight for more than 30 days. Insulate or sleeve exposed runs and store pipes in the shade on site.

Thermal expansion

Plain PP-R expands 1.5 mm per 10 m of pipe per °C (catalogue value; coefficient 1.5 × 10⁻⁴ 1/K). A 20 m run heated by 40 °C therefore grows about 120 mm. Glass-fibre composite PP-R reduces this to 0.4 mm per 10 m per °C. On long horizontal runs plan expansion loops, fixed points and clip spacing — our catalogue lists approximate support spacing by diameter and temperature.

Bottom line

For rigid, welded distribution networks with many fittings — typical of Gulf and Iraqi apartment and commercial buildings — PP-R with fusion joints is a robust, widely available choice. PEX suits flexible runs and manifold systems where mechanical fittings are preferred. Many projects use both.

Frequently asked questions

Can PP-R be used for hot water at 70 °C?

Yes, with the right class: per DIN 8077 PN20 PP-R is rated 8.5 bar at 70 °C for 50 years. Check your system pressure against that value.

Sources

  1. ISO 15874-2:2013 Plastics piping systems for hot and cold water installations — Polypropylene (PP) — Part 2: Pipes — https://www.iso.org/standard/54155.html
  2. ISO 15875-1:2025 Plastics piping systems for hot and cold water installations — Crosslinked polyethylene (PE-X) — Part 1: General — https://www.iso.org/standard/79775.html
  3. Plastics Pipe Institute — PEX Plumbing Design and Installation Guide, Ch. 5 Joining Methods ("PEX tubing cannot be joined by solvent cementing or typical heat fusion methods") — https://plasticpipe.org/common/Uploaded%20files/Technical/PEX%20Plumbing%20Design%20Installation%20Guide%20Third%20Edition_Ch5.pdf
  4. Plastics Pipe Institute — PEX Plumbing Design and Installation Guide, Ch. 9 (UV exposure) — https://plasticpipe.org/common/Uploaded%20files/Technical/PEX%20Plumbing%20Design%20Installation%20Guide%20Third%20Edition_Ch9.pdf
  5. Plastics Pipe Institute — MS-8 Model Specification for PP pressure pipe systems (UV protection, heat-fusion joining) — https://plasticpipe.org/common/Uploaded%20files/Technical/PPI-MS-08.pdf
  6. DIN 8077 permissible operating pressure table for PP-R pipes, safety factor 1.5 (as published by SPK Boru) — https://www.spk.com.tr/en/Article/38663
  7. BR BORLINE PP-R Pipes & Fittings catalogue, October 2026 (product codes, sizes, pack quantities, technical data, welding table) — https://erp.brborline.com/kataloglar
Get a quote / proformaOnline catalogue+90 554 843 46 56info@brborline.com